Installation and Wiring
47
Panel Cut-out Dimensions and Installation
Inserting a GP unit Without an Anti-rotation Tee
Create a panel cut-out and insert the display module of the unit into the panel from
the front. The following illustration shows the panel cut-out for a GP unit without a
tee:
Dimensions
NOTE: Without the tee option, the rotating torque that can be supported by the
display module is 2.5 N•m (22.12 in-lb).
Unit A (mm) A (in.) B (mm) (1) B (in.) (1) B (mm) (2) B (in.) (2)
GP-4201TM
GP-4301TM
+0
22.50
-0.30
+0
0.88
-0.01
1.5 to 6 0.06 to 0.23 3 to 6 0.11 to
0.23
The Material of the panel
(1) Steel sheet
(2) Glass fiber reinforced plastics (minimum GF30)